XGN-12(HT-safe) box type fixed AC metal-enclosed switchgear


Skype: mark2002719  email : mark@cncele.com
XGN-12(HT-safe) box type fixed AC metal-enclosed switchgear
XGN-12(HT-safe) box type fixed AC metal-enclosed switchgear is suitable for a power system of three-phase AC 50HZ, rated voltage 3.6-12KV. It is a sulfur hexafluoride (SF6) all-insulated loop network cabinet and its high voltage live part is totally enclosed in the sulfur hexafluoride box. With small volume, high safety, easy operation, maintenance-free, etc., it is widely used in the fields of real estate, industrial and mining enterprises, and urban grid reconstruction etc, and is especially suitable for a high-voltage distribution systems of high humidity, high dust and other severe environments. In addition, in the high voltage distribution network field, the sulfur hexafluoride (SF6) fully-insulated loop network cabinet is wildly used in high-voltage cable branch box outdoor due to its high safety and maintenance free. The switchgear conforms to IEC60298, GB11022, GB3906, GB1984, GB3804 and other standards.

2. Environmental Conditions for Use
a. Altitude shall not exceed 1,000m;
b. Ambient temperature: +40-35
c. Relative humidity: daily average value shall be no more than 95% and monthly average value shall be no more than 90%;
d. No frequent violent vibration.
3. Main Technical Parameters
3.1 Technical parameters of load switch cabinet (Unit C)
No.
Item
Unit
Parameters
1
Rated voltage
KV
12
2
Rated frequency
Hz
50
3
Rated current
A
630
4
Rated short-time power frequency withstand voltage
Voltage to earth, voltage between phases
KV
42
Isolating fracture
48
5

Rated lightning impulse withstand voltage
Voltage to earth, voltage between phases
KV
75
Isolating fracture
85
6
Rated short-time withstand current
Main circuit 4s
KA
20
Earthing switch 4s
Earthing connection circuit 2s
KA
17.4
7
Rated peak withstand current
Main circuit
KA
50
Earthing switch
Earthing connection circuit
KA
43.5
8

Rated short-circuit making current (peak)
Load switch
KA
50

9
Rated active load breaking current of load switch (I1)
A
630
10
Rated closed loop breaking current of load switch (I2a)
A
630
11
5% rated active load breaking current of load switch (5%I1)
A
31.5
12
Rated cable charging breaking current of load switch (I4a)
A
10
13
Rated active load breaking times of load switch
Times
10
14
Rated earth fault breaking current (I6a) and breaking times
A
31.510次)
31.5(10 times)
15
Rated cable charging and circuit charging breaking current (I1) and breaking times in earth fault condition
A
17.310次)
17.3(10 times)
16
Mechanical life
Load switch
Times
5000
17
Earthing switch
Times
2000
18
Rated pressure of SF6 gas (20, gage pressure)
MPa
0.045
19
Leakage rate of SF6 gas
Year
0.25/千分
0.25/1000 minutes
20
Protection level
IP67
IP3X; IP67 for SF6 gas room and fuse
3.2 Technical parameters of load switch-fuse combination electrical cabinet (Unit F)
No.
Item
Unit
Parameters
1
Rated voltage
KV
12
2
Rated frequency
Hz
50
3
Rated current (main busbar)
A
630
4
A
125
5
Rated short-time power frequency withstand voltage
Voltage to earth, voltage between phases
KV
42
Isolating fracture
48
6
Rated lightning impulse withstand voltage
Voltage to earth, voltage between phases
KV
75
Isolating fracture
85
7
Rated active load breaking current of load switch (I1)
A
630
8
Rated breaking current of combination apparatus
A
31.5
9
Rated transfer current of combination apparatus
A
1,750
10
Mechanical life
Load switch
Times
5,000
11
Earthing switch
Times
2,000
12
Rated pressure of SF6 gas (20, gage pressure)
MPa
0.045
13
Leakage rate of SF6 gas
Year
0.25/千分
0.25/1000 minutes
14
Protection level
IP3X,SF6 IP67
IP3X; IP67 for SF6 gas room and fuse